Indoor Air Quality Reports
Monomoy Regional Middle School Indoor Air Quality
This chart reviews the air quality testing done at Monomoy Middle School, along with the recommendations for remediation from the experts and the steps taken to implement those recommendations. The information is presented in reverse chronological order, with the most recent testing listed at the top.
Reason for Testing |
Date of Testing |
Description |
Conducted By |
Summary of Findings |
District Response |
Report Link |
Periodic precautionary air tests
|
December 2024 |
Air quality test in three locations in the building and three external locations for comparison |
Frank Zelinski of Safe-n-Dry |
See Report Link for details | Further cleaning and investigation of areas with the highest readings, investigating possible leaks under the sink and if necessary removing part of the sink in room B125. Ensure air purifiers already in place are functioning and filters are being replaced on schedule, explore the need for further air purifiers. |
Dec2024 |
Staff Inquiry/ Window Leak |
November 20, 2024 |
Inspection of library – visual and surface samples |
Marina Brock, Soteria, EHS |
Elevated moisture on flooring near previous water intrusion, water-damaged books, some aspergillus detected but levels and state-suggested remediation of moisture had been effective. |
Disposal of damaged books. Monitoring of impacted areas to ensure they dry out and no mold is detected. Routine inspections for mold. Cleaning, clearing of storage areas to minimize risk of mold.
|
|
Staff Inquiry/ Post-Abatement Tests |
November 13, 2024 |
Air tests from room E119 (post-abatement) |
Frank Zelinski of Safe-n-Dry |
Significant reduction to levels of spores detected. |
Ongoing cleaning and air purification. |
|
Staff Inquiry |
November 4, 2024 |
Air tests from room E119 |
Frank Zelinski of Safe-n-Dry |
Some levels of Aspergillus detected, some other spore type levels similar or lower than control (exterior) tests. |
Enhanced cleaning of room. Repair to flooring beneath cabinet (gap in concrete slab). Replacement of window sills. |
|
Staff Inquiry |
September 11, 2024 |
Following reports of mold in classroom, further mold tests (surface and air) were conducted |
Frank Zelinski of Safe-n-Dry |
Airborne mold spores extremely low/non-existent. High levels of Cladosporium in some surface tests. |
Focused cleaning / HEPA vacuum of classroom. Continuing use of air purifiers. |
|
Summer 2024 Post-Remediation Testing |
August 21, 2024 |
Testing to confirm success of remediation |
Frank Zelinski of Safe-n-Dry |
Improved air quality and no evidence of stachybotrys. Some areas continue to have elevated levels of Aspergillus and Cladosporium. |
Continue with increased surface cleaning of targeted areas. Installation of air purifiers. |
|
Summer 2024 Testing and Remediation |
July 30, 2024 |
Testing in response to visible mold and discoloration of ceiling tiles and presence of humidity in building |
Frank Zelinski of Safe-n-Dry |
Results varied by location. However, some samples showed high levels of Aspergillus and Cladosporium. Surface tests of ceiling tiles and wall in room E114 found evidence of stachybotrys |
Abatement of mold in ceiling tiles and drywall: The district contracted with ServPro to remove ceiling tiles from the main office and the SROs office, as well as a section of drywall from room E114. Installation of additional air purifiers. Additional surface cleaning. Survey of window sills, and removal and replacement of most damaged sills. |
|
Siding Replacement Project |
July 29-31, 2024 |
Testing of the building envelope: These tests were conducted as part of the siding replacement project |
Raymond Design Associates (Architectural firm), and sub-contractors |
Evidence of water damage and water intrusion around windows. Indoor air quality within acceptable human comfort range however concerns related to ventilation system and water damage. |
Long-term project to replace building siding and roof. Survey, repair, and maintenance of exhaust fans in classrooms. Removal and replacement of window sills. Patching of building exterior where possible. |
|
Concern around perceived dampness | October 27, 2023 | Limited indoor air quality sampling and a visual assessment. | Vertex Companies LLC | General IAQ parameters appeared to be within acceptable human comfort range for temperature and Carbon Dioxide, and humidity was higher than recommended levels to minimize mold growth. Water damage was observed, but areas of suspected visible mold growth were not observed. | Removal and replacement of water-damaged materials (internal/external), and HVAC maintenance and repairs, increased ue of dehumidifiers. |
Oct2023-2 |
Staff Inquiry |
October 26, 2023 |
Visual and odor inspection of room E114 |
Marina Brock, Barnstable County |
Odor detected in room E114 and office space. Concerns raised about flooring, lack of sealant in classroom storage and concrete slab. |
Installation of flooring beneath classroom cupboards to act as a barrier between the classroom and the concrete slab. |
|
Staff Inquiry |
September 19, 2023 |
Indoor Air Quality tests (CO2, CO, Humidity, Temperature) and surface area tests. (room B136 and adjacent rooms) |
Marina Brock, Barnstable County |
No identified flowering or viable mold growth detected, concerns raised about the condition of the carpet. |
Replacement of carpet. Removal of tree/organic matter outside of room. Operation of dehumidifier and air filter. Cleaning and removal of clutter, debris from other classrooms. |
|
Staff Inquiry |
December 16, 2022 |
Investigation of classroom odor. Visual inspection, moisture testing. |
Marina Brock, Barnstable County |
Strong smell of mildew, appeared to come from uninvent, identification of damp building exterior. |
Maintenance of ventilation system. Further investigation of building exterior. |
|
Staff Inquiry |
June 21, 2022 |
Visual and odor inspection of two science classrooms. |
Marina Brock, Barnstable County |
No evidence of mold found. |
Ongoing project to replace carpet throughout building. |
|
Staff Inquiry |
September 2, 2021 |
Visual test and surface tests of science labs. |
Marina Brock, Barnstable County |
Cladosporium found on seat of an upholstered chair and in small area on floor next to wall. Saprophytic fungi (Rhizopus) found on carpet. |
Enhanced cleaning and decluttering of room. |
|
Staff Inquiry | January 11, 2020 | Air quality test in RM E114, E112, and outside | Universal Environmental Consultants |
Some increased levels of aspergillus/ penicllum in one area (rm E114, by board), otherwise similar to outside levels. |
Cleaning and further investigation | Jan2020 |